1: I'm getting the
"Pending" message. What's wrong?
For
DataWorx PLC
Standard and Professional
First confirm that
the ECOM module is visible on the network. Use NetEdit to browse
for the ECOM. Note that when using NetEdit use the UDP/IP
protocol. If you are unable to view the ECOM with NetEdit confirm
that the ECOM is plugged into the network cable. Also, the IP
address of the ECOM may be out of range for your network. Consult
with the network administrator on the appropriate IP address
ranges. By default most plant networks use a 192.168.0.X range.
Second, confirm
that the WX command has the appropriate configuration. To do so
start DataWorx and go to the PLC's configuration. Click the Configure PLC
Memory button and enter the desired V
Memory locations. Then, click Autoconfigure, and the PLC
memory should be configured for the WX command. Note that if the
DataWorx server has multiple NICs you will have to disable all cards
except for the one used for DataWorx. For more details see FAQ
2: I have multiple NICs; which one do I use for DataWorx?
Third, confirm the
slot number of the ECOM is correct on the PLC. You can do this by going
to the DirectSoft menu: PLC -> Configure IO. The slot number
(#) of the
ECOM will be displayed.
Fourth, if you have
Windows XP Service Pack 2 you may have to disable the firewall. By
default, the firewall blocks the PLC data. To disable the firewall,
go to the NIC properties. Click the Advanced tab and you
should see a Windows Firewall section. Click Settings
and you should see a window displaying options for On and Off. Click
Off and
click OK on the previous screens.
For
DataWorx WinPLC
Standard and Professional
First,
confirm that
the WinPLC is visible on the plant network. To do so run ESP or
CEView. Click the Select CE Station button. If
you do not see the WinPLC, it may have to be reset to a different IP
address. To do so, connect the WinPLC to the PC using a crossover
cable. Next, use the Reset WinPLC in the Browse WinPLCs window.
Second,
confirm
that the flowchart is writing to the correct address. To do so, go
to IOView and view the target CE device properties. The
target CE device IP address should be the same as the DataWorx
computer. Note that you can quickly retrieve the DataWorx computer
IP address by opening the Server application.
Third, if you have
Windows XP Service Pack 2 you may have to disable the firewall because
by default it blocks the PLC data. To disable the firewall, go to the NIC properties. Click
the Advanced tab, and you
should see a Windows Firewall section. Click Settings,
and you should see a window displaying options for On and Off. Click
Off and
click OK on the previous screens.
FAQ
2: I have multiple NICs; which one do I use for DataWorx?
In order to determine the appropriate NIC for DataWorx,
you will have
to use ipconfig. To use ipconfig, click the Start button and
choose Run. In the box that appears enter "cmd"
(no quotes). You will then see a black window. Enter
"ipconfig /all" (no quotes). You will then see a list
of all NICs and their corresponding IP addresses. The one to be
used for DataWorx will have a similar IP address to the PLCs. For
example, if the PLCs IP address is 10.1.1.2, then the appropriate NIC on
the computer will have an IP address of 10.1.1.5.
If you are still unsure of the appropriate NIC to use for DataWorx,
consult with the plant network administrator.
FAQ
3: I'm having a
hard time registering the product, can you help me?
Go to
Help -> Registration in the DataWorx
Monitor menu. You will see a Registration
window with a field labeled "Key." This Key is a special
registration code created
just for you. Copy the key, either by using Ctrl + C or by right-clicking the mouse and selecting
Copy. Next, go to: www.bizwaredirect.com/dataworxregistration.aspx.
Paste the key into the field labeled "Key (From DataWorx
Install)." Next, enter the serial number that is on the back of
the software case provided with the DataWorx product.
Click
Register. If all fields have been entered correctly, a new key
which has been created for you will appear onscreen. Copy this new key and go
back to the DataWorx Monitor Registration screen. Paste the new key into
the Key field. Also enter the serial number that is on the
back of the software case provided with the DataWorx product into the
correct field. Click Register. If all information has been
entered correctly into the appropriate fields, a box should appear
onscreen, indicating that your software has been registered
successfully.
FAQ
4: Doesn't this product work like DSData or KEPDirect?
DSData and
KEPDirect are polling products, which gather data from the PLCs on a
constant interval. Through this continuous polling method, the computer requests data from the PLC
and the PLC responds with the data. DataWorx, on the other hand, uses report-by-exception technology.
Report by exception allows the PLC to send data to the
computer. This architecture assures that the computer will log data only when
needed.
As an example to
illustrate this concept, let's say that you wanted to log the number of bottles
processed per hour in a bottle plant. With a polling product, such
as DSData and KEPDirect, the computer will ask for the number of bottles
processed every second instead of every hour. This is wasteful of
bandwidth and can create scaling problems with a plant containing
multiple devices.
With DataWorx,
however, the
PLC would be programmed in the ladder logic to send data every hour
using a timer. With DataWorx's report-by-exception technology, the data is transmitted only once per hour,
instead
of the once every second that you would see with polling. This
provides a more efficient use of bandwidth and allows scaling to more
devices compared to polling.
So, overall
DataWorx allows the PLC to have complete control over the data sending
and it allows data to be sent ONLY when needed.
FAQ 5: How do I log data to an Access 2007 database?
If you need to log data to an Access 2007 or 2010 database, you must either
install Access 2007/2010 or the Microsoft Access Database Engine
on to the DataWorx server.
The Microsoft Access Database Engine may be downloaded
from Microsoft at the following link (called 2007 Office System Driver: Data Connectivity Components):
http://www.microsoft.com/downloads/en/details.aspx?FamilyID=7554f536-8c28-4598-9b72-ef94e038c891
The Microsoft Access Database Engine 2010 may be downloaded
from Microsoft at the following link:
http://www.microsoft.com/downloads/en/details.aspx?FamilyID=C06B8369-60DD-4B64-A44B-84B371EDE16D
Back
to DataWorx Standard Main Product Page
Back
to DataWorx Professional Main Product Page
Ask
a Question
|